Thermal Overload Relay JLR2-D13
Motion Characteristic: Three-phase Balance Motion Time
No | Tiden fan de ynstelstroom (A) | Motion tiid | Start betingst | Omjouwingstemperatuer | ||
1 | 1.05 | >2h | Kâlde steat | 20±5°C
| ||
2 | 1.2 | <2h | Heat steat | |||
3 | 1.5 | <4 min | (Nei de No.l test) | |||
4 | 7.2 | 10A | 2s | <63A | Kâlde steat | |
10 | 4s | >63A |
Fase-ferlies Motion Characteristic
No | Tiden fan de ynstelstroom (A) | Motion tiid | Start betingst | Omjouwingstemperatuer | |
Elke twa fazen | In oare faze | ||||
1 | 1.0 | 0.9 | >2h | Kâlde steat | 20±5°C |
2 | 1.15 | 0 | <2h | Heat steat (Nei de No.l test) |
Spesifikaasje
Type | Nûmer | Ynstellingsberik (A) | Foar kontaktor |
JLR2-D13
| 1301 | 0.1~0.16 | JLC1-09~32 |
1302 | 0.16~0.25 | JLC1-09~32 | |
1303 | 0.25~0.4 | JLC1-09~32 | |
1304 | 0.4~0.63 | JLC1-09~32 | |
1305 | 0.63~1 | JLC1-09~32 | |
1306 | 1~1.6 | JLC1-09~32 | |
1307 | 1.6~2.5 | JLC1-09~32 | |
1308 | 2.5~4 | JLC1-09~32 | |
1310 | 4~6 | JLC1-09~32 | |
1312 | 5.5~8 | JLC1-09~32 | |
1314 | 7~10 | JLC1-09~32 | |
1316 | 9~13 | JLC1-09~32 | |
1321 | 12~18 | JLC1-09~32 | |
1322 | 17~25 | JLC1-32 | |
JLR2-D23
| 2353 | 23~32 | CJX2-09~32 |
2355 | 30~40 | JLC1-09~32 | |
JLR2-D33
| 3322 | 17~25 | JLC1-09~32 |
3353 | 23~32 | JLC1-09~32 | |
3355 | 30~40 | JLC1-09~32 | |
3357 | 37~50 | JLC1-09~32 | |
3359 | 48~65 | JLC1-09~32 | |
3361 | 55~70 | JLC1-09~32 | |
3363 | 63~80 | JLC1-09~32 | |
3365 | 80~93 | JLC1-95 | |
JLR2-D43
| 4365 | 80~104 | JLC1-95 |
4367 | 95~120 | JLC1-95~115 | |
4369 | 110~140 | JLC1-115 |
Outline En Montage Ofmjitting
Accessories
Applikaasje senario:
Meastentiids ynstalleare yn 'e distribúsjekast op' e flier, kompjûtersintrum, telekommunikaasjekeamer, liftkontrôlekeamer, kabel TV-keamer, geboukontrôlekeamer, brânsintrum, yndustriële automatyske kontrôlegebiet, sikehûsoperaasjekeamer, tafersjochkeamer en distribúsjekastapparatuer mei elektroanysk medysk apparaat .